PULS
YR2.DIODE
Dual-input redundancy module (2 x inputs + 1 x output) with diode technology + ATEX approval - PULS (DIMENSION Y-series) - 12-48Vdc (12Vdc / 24Vdc / 48Vdc nom.) / 20A output - with spring-clamp connections - DIN rail mounting (32mm width) - equivalent to #YR2DIODE
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
YR2.DIODE
Online Price
$110.00
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
YR2.DIODE
Description
Dual-input redundancy module (2 x inputs + 1 x output) with diode technology + ATEX approval - PULS (DIMENSION Y-series) - 12-48Vdc (12Vdc / 24Vdc / 48Vdc nom.) / 20A output - with spring-clamp connections - DIN rail mounting (32mm width) - equivalent to #YR2DIODE
Specifications
Primary brand
PULS
Main function
Redundancy unit
Product series / family name
DIMENSION series
Sub-range name
Y-series
Functions
Dual-input redundancy module (2 x inputs + 1 x output)
Design
diode technology
ATEX approval
ATEX approval
Supply voltage (DC)
9Vdc-60Vdc (12Vdc / 24Vdc / 48Vdc nom.)
Rated current
20A (at 48Vdc)
0.5A/+60°C...+70°C (derating)
0.5A/+60°C...+70°C (derating)
Output voltage (DC)
12-48Vdc (12Vdc / 24Vdc / 48Vdc nom.)
Connection type
spring-clamp connections
Protection functions
short-circuit protection (25A threshold at 6V)
Series / parallel operation -- 1+1 Redundancy Use of 2 identical power supplies in parallel to provide continued operation following most failures in a single power supply. The 2 power supply outputs should be isolated from each other by utilizing diodes or other switching arrangements. N+1 Redundancy Use of 3 or more identical power supplies in parallel to provide continued operation following most failures in a single power supply. All power supply outputs should be isolated from each other by utilizing diodes or other switching arrangements.
Series / parallel operation -- 1+1 Redundancy Use of 2 identical power supplies in parallel to provide continued operation following most failures in a single power supply. The 2 power supply outputs should be isolated from each other by utilizing diodes or other switching arrangements. N+1 Redundancy Use of 3 or more identical power supplies in parallel to provide continued operation following most failures in a single power supply. All power supply outputs should be isolated from each other by utilizing diodes or other switching arrangements.
Mounting mode
DIN rail mounting
Dimensions
W32mm x H124mm x D102mm
Net Width (mm)
32 mm
Ambient air temperature for operation
-40...+70 °C
Current consumption
150A peak max. inrush (at 9-60Vdc input)
Technical compatibility with
Diode
Power dissipation/losses
(9-60Vdc input; 2x5A input) 7.8 W
(9-60Vdc input; 2x10A input) 17 W
(9-60Vdc input; 2x10A input) 17 W
Manufacturer product status
Commercialized
Equivalent to
YR2DIODE
Compliant with standard(s)
CE marking
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
IECEx
ATEX
Class I Div. 2 HazLoc
GL Marine
ABS Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
IECEx
ATEX
Class I Div. 2 HazLoc
GL Marine
ABS Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
Electrical durability
(at 40°C; 20A output; 2x5A/10A input) 25years / 219000 hours
(at 25°C; 10A output; 2x5A/10A input) 25years / 219000 hours
(at 25°C; 10A output; 2x5A/10A input) 25years / 219000 hours
Benefits
Cost effective solution to build redundant systems
Dual input with single output
2 diodes (common cathode)
DC 12-48V wide-range input
Full power between -40°C and +60°C
Width only 32mm
Rugged metal housing
Quick-connect spring-clamp terminals
Easy wiring;
Distribution terminal for negative pole included
3 Year warranty
The YR2.DIODE is a redundancy module which can be used to build 1+1 and N+1 redundant system. It is equipped with 2 input channels which can be connected to power supplies with up to 10A output current and 1 output which can carry nominal currents up to 20A. The module is suitable for power supplies with constant current overload behaviour as well as any kind of Hiccup overload behaviour. The YR2.DIODE is the perfect solution to use in a redundant system if the power supply itself is equipped with a DC-OK signal (e.g.; DIMENSION Q-Series). In addition to the YR2.DIODE is the YRM2.DIODE which has a monitoring circuitry included. LEDs and relay contacts signal when 1 of the 2 DC-input voltages is not in range due to a non-functioning power supply. Another interesting application for this redundancy module is to separate sensitive loads from non-sensitive loads. This avoids the distortion of the power quality for the sensitive loads which can cause controller failures. Unique quick-connect spring-clamp terminals allow a safe and fast installation and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Dual input with single output
2 diodes (common cathode)
DC 12-48V wide-range input
Full power between -40°C and +60°C
Width only 32mm
Rugged metal housing
Quick-connect spring-clamp terminals
Easy wiring;
Distribution terminal for negative pole included
3 Year warranty
The YR2.DIODE is a redundancy module which can be used to build 1+1 and N+1 redundant system. It is equipped with 2 input channels which can be connected to power supplies with up to 10A output current and 1 output which can carry nominal currents up to 20A. The module is suitable for power supplies with constant current overload behaviour as well as any kind of Hiccup overload behaviour. The YR2.DIODE is the perfect solution to use in a redundant system if the power supply itself is equipped with a DC-OK signal (e.g.; DIMENSION Q-Series). In addition to the YR2.DIODE is the YRM2.DIODE which has a monitoring circuitry included. LEDs and relay contacts signal when 1 of the 2 DC-input voltages is not in range due to a non-functioning power supply. Another interesting application for this redundancy module is to separate sensitive loads from non-sensitive loads. This avoids the distortion of the power quality for the sensitive loads which can cause controller failures. Unique quick-connect spring-clamp terminals allow a safe and fast installation and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Ripple
800mVpp (20Hz...20MHz; 50Ω)
MTBF (Mean Time Between Failures)
46500000h (at 40°C; 2x10A input; MTBF SN 29500 IEC 61709)
55700000h (at 40°C; 2x5A input; MTBF SN 29500 IEC 61709)
70000000h (at 25°C; 2x10A input; MTBF SN 29500 IEC 61709)
84000000h (at 25°C; 2x5A input; MTBF SN 29500 IEC 61709)
36200000h (at 40°C; 2x10A input; MTBF MIL HDBK 217F)
43500000h (at 40°C; 2x5A input; MTBF MIL HDBK 217F)
41100000h (at 25°C; 2x10A input; MTBF MIL HDBK 217F)
49300000h (at 25°C; 2x5A input; MTBF MIL HDBK 217F)
55700000h (at 40°C; 2x5A input; MTBF SN 29500 IEC 61709)
70000000h (at 25°C; 2x10A input; MTBF SN 29500 IEC 61709)
84000000h (at 25°C; 2x5A input; MTBF SN 29500 IEC 61709)
36200000h (at 40°C; 2x10A input; MTBF MIL HDBK 217F)
43500000h (at 40°C; 2x5A input; MTBF MIL HDBK 217F)
41100000h (at 25°C; 2x10A input; MTBF MIL HDBK 217F)
49300000h (at 25°C; 2x5A input; MTBF MIL HDBK 217F)
Related Documents
Name | Last Update | Language |
---|---|---|
PULS - Power supply units - Catalog.pdf | 01 Oct 2021 | English (US) |
PULS - YR2-DIOD--1 - Datasheet.pdf | 01 Oct 2021 | English (US) |