PULS
SLA8.100
AS-Interface power supply unit (PSU) - PULS (SilverLine) - 8A output - with screw-clamp connections - Single-phase (1AC) or DC input (85Vac-132Vac / 187Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 240Vac nom.; 47-63Hz) (manual select) / 230Vdc-375Vdc (250Vdc)) - DIN rail mounting (91mm width) - equivalent to #SLA8100
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
SLA8.100
Online Price
$840.00
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
SLA8.100
Description
AS-Interface power supply unit (PSU) - PULS (SilverLine) - 8A output - with screw-clamp connections - Single-phase (1AC) or DC input (85Vac-132Vac / 187Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 240Vac nom.; 47-63Hz) (manual select) / 230Vdc-375Vdc (250Vdc)) - DIN rail mounting (91mm width) - equivalent to #SLA8100
Specifications
Primary brand
PULS
Main function
Power supply unit
Product series / family name
SilverLine series
Functions
AS-Interface power supply unit (PSU)
Design
DC-OK rly. contact output
Supply voltage (AC)
85Vac-132Vac / 187Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 240Vac nom.; 47-63Hz) (manual select)
Supply voltage (DC)
230Vdc-375Vdc (250Vdc)
Display
"DC-OK" LED
Type of network
Single-phase (1AC) or DC
Rated current
8A (at 30.6Vdc)
6W/+60°C...+70°C (derating)
6W/+60°C...+70°C (derating)
Output voltage (DC)
30.6Vdc (fixed voltage)
Hold time
10ms (buffer time at 100Vac input)
Connection type
screw-clamp connections
Protection functions
output overvoltage protection (55Vdc max.)
active (input inrush current limiter)
Overload / short-circuit current -- min. 12A / max. 25A current
Series / parallel operation -- not possible
active (input inrush current limiter)
Overload / short-circuit current -- min. 12A / max. 25A current
Series / parallel operation -- not possible
Efficiency
0.92 (230Vac input)
Net Width (mm)
91 mm
Mounting mode
DIN rail mounting
Dimensions
W91mm x H124mm x D102mm
Material
Robust metal housing
Ambient air temperature for operation
-10...+70 °C
Current consumption
27A peak max. inrush (at 240Vac input)
14A peak max. inrush (at 120Vac input)
14A peak max. inrush (at 120Vac input)
Power dissipation/losses
(230Vac input; full output load) 21.2 W
Power factor (cos phi)
(230Vac input) 0.5
Manufacturer product status
Commercialized
Equivalent to
SLA8100
Compliant with standard(s)
SN 29500
CE marking
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
CE marking
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
Benefits
AS Interface data decoupling
Infrared (IR) addressing mode
Overload protection by FUSE Mode
For highly demanding industrial applications
Infrared (IR) addressing mode
Overload protection by FUSE Mode
For highly demanding industrial applications
Ripple
50mVpp (20Hz...20MHz; 50Ω)
MTBF (Mean Time Between Failures)
869000h (at +40°C)
Related Documents
Name | Last Update | Language |
---|---|---|
PULS - Power supply units - Catalog.pdf | 01 Oct 2021 | English (US) |
PULS - SLA8-100 - Datasheet.pdf | 01 Oct 2021 | English (US) |