PULS
CS5.241-S1
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION C-Line series) - 5A (at 24Vdc; ambient less than 60°C) - 24Vdc-28Vdc (adjustable) / 6A / 120W output - with spring-clamp connections - Single-phase (1AC) input (85Vac-132Vac / 184Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) (auto select)) - DIN rail mounting (32mm width) - equivalent to #CS5241S1
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
CS5.241-S1
Online Price
$260.00
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
CS5.241-S1
Description
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION C-Line series) - 5A (at 24Vdc; ambient less than 60°C) - 24Vdc-28Vdc (adjustable) / 6A / 120W output - with spring-clamp connections - Single-phase (1AC) input (85Vac-132Vac / 184Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) (auto select)) - DIN rail mounting (32mm width) - equivalent to #CS5241S1
Specifications
Primary brand
PULS
Main function
Power supply unit
Product series / family name
DIMENSION series
Sub-range name
C-Line series
Functions
AC/DC Power supply unit (PSU) / converter
20% power reserve
20% power reserve
Design
20% power reserve
DC-OK rly. contact output
DC-OK rly. contact output
Supply voltage (AC)
85Vac-132Vac / 184Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) (auto select)
75Vac turn-ON voltage
55Vac shutdown voltage (steady-state)
75Vac turn-ON voltage
55Vac shutdown voltage (steady-state)
Display
"DC-OK" LED
Type of network
Single-phase (1AC)
Rated current
6A (at 24Vdc; ambient less than 45°C)
5A (at 24Vdc; ambient less than 60°C)
5.1A (at 28Vdc; ambient less than 45°C)
4.3A (at 28Vdc; ambient less than 60°C)
5A (at 24Vdc; ambient less than 60°C)
5.1A (at 28Vdc; ambient less than 45°C)
4.3A (at 28Vdc; ambient less than 60°C)
Rated power
144W (ambient less than 45°C)
120W (ambient less than 60°C)
120W (ambient less than 60°C)
Output voltage (DC)
24Vdc-28Vdc (adjustable)
400mV turn-ON overshoot
400mV turn-ON overshoot
Hold time
78ms (buffer time at 230Vac input)
80ms (buffer time at 120Vac input)
80ms (buffer time at 120Vac input)
Connection type
spring-clamp connections
Protection functions
output overvoltage protection (34Vdc typ. / 39Vdc max.)
active (input inrush current limiter)
Overload / short-circuit current -- min. 10A (max. 14A) at load impedance <200mΩ
Series / parallel operation -- Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case 1 power supply unit fails. The simplest way is to put 2 power supplies in parallel. This is called a 1+1 redundancy. In case 1 power supply unit fails the other 1 is automatically able to support the load current without any interruption
Back-feeding loads max. 35V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
active (input inrush current limiter)
Overload / short-circuit current -- min. 10A (max. 14A) at load impedance <200mΩ
Series / parallel operation -- Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case 1 power supply unit fails. The simplest way is to put 2 power supplies in parallel. This is called a 1+1 redundancy. In case 1 power supply unit fails the other 1 is automatically able to support the load current without any interruption
Back-feeding loads max. 35V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
Efficiency
0.902 (230Vac input)
0.894 (120Vac input)
0.888 (100Vac input)
0.894 (120Vac input)
0.888 (100Vac input)
Mounting mode
DIN rail mounting
Time delay
740-900ms start-up delay (100-230Vac input)
8ms rise time (nominal input; constant full current load; 0mF load capacitance)
25ms rise time (nominal input; constant full current load; 5mF load capacitance)
8ms rise time (nominal input; constant full current load; 0mF load capacitance)
25ms rise time (nominal input; constant full current load; 5mF load capacitance)
Dimensions
W32mm x H124mm x D117mm
Net Width (mm)
32 mm
Material
Aluminium housing
Ambient air temperature for operation
-25...+70 °C
Current consumption
1.23A (230Vac input; full 24Vdc output)
2A (120Vac input; full 24Vdc output)
2.33A (100Vac input; full 24Vdc output)
10A peak max. inrush (at 230Vac input)
10A peak max. inrush (at 120Vac input)
10A peak max. inrush (at 100Vac input)
2A (120Vac input; full 24Vdc output)
2.33A (100Vac input; full 24Vdc output)
10A peak max. inrush (at 230Vac input)
10A peak max. inrush (at 120Vac input)
10A peak max. inrush (at 100Vac input)
Power dissipation/losses
(230Vac input; full output load) 13.2 W
(120Vac input; full output load) 14.5 W
(120Vac input; full output load) 14.5 W
Power factor (cos phi)
(230Vac input) 0.47
(120Vac input) 0.56
(120Vac input) 0.56
Manufacturer product status
Commercialized
Equivalent to
CS5241S1
Capacitance
(output stage) 1800 μF
Compliant with standard(s)
CE marking
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
Class I Div. 2 HazLoc
GL Marine
ABS Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
Class I Div. 2 HazLoc
GL Marine
ABS Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
Electrical durability
(at 40°C; 2.5A output; 1AC 120Vac input) 128000 hours
(at 40°C; 2.5A output; 1AC 230Vac input) 144000 hours
(at 25°C; 2.5A output; 1AC 120Vac input) 363000 hours
(at 25°C; 2.5A output; 1AC 230Vac input) 408000 hours
(at 40°C; 5A output; 1AC 120Vac input) 58000 hours
(at 40°C; 5A output; 1AC 230Vac input) 72000 hours
(at 25°C; 5A output; 1AC 120Vac input) 163000 hours
(at 25°C; 5A output; 1AC 230Vac input) 204000 hours
(at 40°C; 6A output; 1AC 120Vac input) 34000 hours
(at 40°C; 6A output; 1AC 230Vac input) 42000 hours
(at 25°C; 6A output; 1AC 120Vac input) 96000 hours
(at 25°C; 6A output; 1AC 230Vac input) 120000 hours
(at 40°C; 2.5A output; 1AC 230Vac input) 144000 hours
(at 25°C; 2.5A output; 1AC 120Vac input) 363000 hours
(at 25°C; 2.5A output; 1AC 230Vac input) 408000 hours
(at 40°C; 5A output; 1AC 120Vac input) 58000 hours
(at 40°C; 5A output; 1AC 230Vac input) 72000 hours
(at 25°C; 5A output; 1AC 120Vac input) 163000 hours
(at 25°C; 5A output; 1AC 230Vac input) 204000 hours
(at 40°C; 6A output; 1AC 120Vac input) 34000 hours
(at 40°C; 6A output; 1AC 230Vac input) 42000 hours
(at 25°C; 6A output; 1AC 120Vac input) 96000 hours
(at 25°C; 6A output; 1AC 230Vac input) 120000 hours
Benefits
AC 100-120 / 200-240V Auto-select Input
Width only 32mm
Optional with Conformal Coated PC-boards (CS5.241-C1)
Optional with Spring-clamp Terminals (CS5.241-S1)
Efficiency up to 90.2%
Easy fuse breaking due to high overload peak current
20% Output power reserve
Full power between -25°C and +60°C
Minimal inrush current surge
3 Year warranty
The DIMENSION C-Line units are cost optimized power supplies without compromising quality reliability and performance. The C-Line is part of the DIMENSION power supply family existing alongside the high featured Q-Line. The CS5.241 includes all the essential basic functions and the devices have a power reserve of 20%. This extra current may even be used continuously at temperatures up to +45°C. The most important features are the small size high efficiency and the wide temperature range. The Auto-select input makes worldwide installation and usage very simple. Defects or system failures caused by wrongly set switches cannot occur. High immunity to transients and power surges as well as low electromagnetic emission and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Width only 32mm
Optional with Conformal Coated PC-boards (CS5.241-C1)
Optional with Spring-clamp Terminals (CS5.241-S1)
Efficiency up to 90.2%
Easy fuse breaking due to high overload peak current
20% Output power reserve
Full power between -25°C and +60°C
Minimal inrush current surge
3 Year warranty
The DIMENSION C-Line units are cost optimized power supplies without compromising quality reliability and performance. The C-Line is part of the DIMENSION power supply family existing alongside the high featured Q-Line. The CS5.241 includes all the essential basic functions and the devices have a power reserve of 20%. This extra current may even be used continuously at temperatures up to +45°C. The most important features are the small size high efficiency and the wide temperature range. The Auto-select input makes worldwide installation and usage very simple. Defects or system failures caused by wrongly set switches cannot occur. High immunity to transients and power surges as well as low electromagnetic emission and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Ripple
50mVpp (20Hz...20MHz; 50Ω)
MTBF (Mean Time Between Failures)
661000h (at 40°C; 120Vac input; MTBF SN 29500 IEC 61709)
869000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
562000h (at 40°C; 120Vac input; MTBF SN 29500 IEC 61709)
739000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
1111000h (at 25°C; 120Vac input; MTBF SN 29500 IEC 61709)
1495000h (at 25°C; 230Vac input; MTBF SN 29500 IEC 61709)
546000h (at 40°C; 120Vac input; MTBF MIL HDBK 217F)
574000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
491000h (at 40°C; 120Vac input; MTBF MIL HDBK 217F)
517000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
775000h (at 25°C; 120Vac input; MTBF MIL HDBK 217F)
800000h (at 25°C; 230Vac input; MTBF MIL HDBK 217F)
869000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
562000h (at 40°C; 120Vac input; MTBF SN 29500 IEC 61709)
739000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
1111000h (at 25°C; 120Vac input; MTBF SN 29500 IEC 61709)
1495000h (at 25°C; 230Vac input; MTBF SN 29500 IEC 61709)
546000h (at 40°C; 120Vac input; MTBF MIL HDBK 217F)
574000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
491000h (at 40°C; 120Vac input; MTBF MIL HDBK 217F)
517000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
775000h (at 25°C; 120Vac input; MTBF MIL HDBK 217F)
800000h (at 25°C; 230Vac input; MTBF MIL HDBK 217F)
Related Documents
Name | Last Update | Language |
---|---|---|
PULS - Power supply units - Catalog.pdf | 01 Oct 2021 | English (US) |
PULS - CS5-241-S1-1 - Datasheet.pdf | 01 Oct 2021 | English (US) |