PULS
CS10.241-S1
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION C-Line series) - 10A (at 24Vdc; ambient less than 60°C) - 24Vdc-28Vdc (adjustable) / 12A / 240W output - with spring-clamp connections - Single-phase (1AC) input (85Vac-132Vac / 184Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) (auto select)) - DIN rail mounting (60mm width) - equivalent to #CS10241S1
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Brand
SKU
CS10.241-S1
Online Price
$461.50
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
CS10.241-S1
Description
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION C-Line series) - 10A (at 24Vdc; ambient less than 60°C) - 24Vdc-28Vdc (adjustable) / 12A / 240W output - with spring-clamp connections - Single-phase (1AC) input (85Vac-132Vac / 184Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) (auto select)) - DIN rail mounting (60mm width) - equivalent to #CS10241S1
Specifications
Primary brand
PULS
Main function
Power supply unit
Product series / family name
DIMENSION series
Sub-range name
C-Line series
Functions
AC/DC Power supply unit (PSU) / converter
20% power reserve
20% power reserve
Design
20% power reserve
DC-OK rly. contact output
DC-OK rly. contact output
Supply voltage (AC)
85Vac-132Vac / 184Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) (auto select)
80Vac turn-ON voltage
75Vac shutdown voltage (steady-state)
80Vac turn-ON voltage
75Vac shutdown voltage (steady-state)
Display
"DC-OK" LED
Type of network
Single-phase (1AC)
Rated current
12A (at 24Vdc; ambient less than 45°C)
10A (at 24Vdc; ambient less than 60°C)
10.3A (at 28Vdc; ambient less than 45°C)
8.6A (at 28Vdc; ambient less than 60°C)
10A (at 24Vdc; ambient less than 60°C)
10.3A (at 28Vdc; ambient less than 45°C)
8.6A (at 28Vdc; ambient less than 60°C)
Rated power
288W (ambient less than 45°C)
240W (ambient less than 60°C)
240W (ambient less than 60°C)
Output voltage (DC)
24Vdc-28Vdc (adjustable)
100mV turn-ON overshoot
100mV turn-ON overshoot
Hold time
47ms (buffer time at 230Vac input)
46ms (buffer time at 120Vac input)
46ms (buffer time at 120Vac input)
Connection type
spring-clamp connections
Protection functions
output overvoltage protection (34Vdc typ. / 39Vdc max.)
active (input inrush current limiter)
Overload / short-circuit current -- min. 14A (max. 18A) at load impedance <100mΩ
Series / parallel operation -- Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case 1 power supply unit fails. The simplest way is to put 2 power supplies in parallel. This is called a 1+1 redundancy. In case 1 power supply unit fails the other 1 is automatically able to support the load current without any interruption
Back-feeding loads max. 35V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
active (input inrush current limiter)
Overload / short-circuit current -- min. 14A (max. 18A) at load impedance <100mΩ
Series / parallel operation -- Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case 1 power supply unit fails. The simplest way is to put 2 power supplies in parallel. This is called a 1+1 redundancy. In case 1 power supply unit fails the other 1 is automatically able to support the load current without any interruption
Back-feeding loads max. 35V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
Efficiency
0.916 (230Vac input)
0.91 (120Vac input)
0.907 (100Vac input)
0.91 (120Vac input)
0.907 (100Vac input)
Net Width (mm)
60 mm
Mounting mode
DIN rail mounting
Dimensions
W60mm x H124mm x D117mm
Material
Aluminium housing
Ambient air temperature for operation
-25...+70 °C
Current consumption
2.23A (230Vac input; full 24Vdc output)
3.73A (120Vac input; full 24Vdc output)
4.34A (100Vac input; full 24Vdc output)
10A peak max. inrush (at 230Vac input)
10A peak max. inrush (at 120Vac input)
10A peak max. inrush (at 100Vac input)
3.73A (120Vac input; full 24Vdc output)
4.34A (100Vac input; full 24Vdc output)
10A peak max. inrush (at 230Vac input)
10A peak max. inrush (at 120Vac input)
10A peak max. inrush (at 100Vac input)
Power dissipation/losses
(230Vac input; full output load) 22 W
(120Vac input; full output load) 23.7 W
(120Vac input; full output load) 23.7 W
Power factor (cos phi)
(230Vac input) 0.51
(120Vac input) 0.59
(120Vac input) 0.59
Manufacturer product status
Commercialized
Equivalent to
CS10241S1
Capacitance
(output stage) 7000 μF
Compliant with standard(s)
CE marking
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
Class I Div. 2 HazLoc
GL Marine
ABS Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
Class I Div. 2 HazLoc
GL Marine
ABS Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
Benefits
AC 100-120 / 200-240V Auto-select Input
Width only 60mm
Optional with Spring-clamp Terminals (CS10.241-S1)
Efficiency up to 91.6%
Easy fuse breaking due to high overload peak current
20% Output power reserve
Full power between -25°C and +60°C
Minimal inrush current surge
3 Year warranty
The DIMENSION C-Line units are cost optimized power supplies without compromising quality reliability and performance. The C-Line is part of the DIMENSION power supply family existing alongside the high featured Q-Line. The CS10.241 includes all the essential basic functions and the devices have a power reserve of 20%. This extra current may even be used continuously at temperatures up to +45°C. The most important features are the small size high efficiency and the wide temperature range. The Auto-select input makes worldwide installation and usage very simple. Defects or system failures caused by wrongly set switches cannot occur. High immunity to transients and power surges as well as low electromagnetic emission and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Width only 60mm
Optional with Spring-clamp Terminals (CS10.241-S1)
Efficiency up to 91.6%
Easy fuse breaking due to high overload peak current
20% Output power reserve
Full power between -25°C and +60°C
Minimal inrush current surge
3 Year warranty
The DIMENSION C-Line units are cost optimized power supplies without compromising quality reliability and performance. The C-Line is part of the DIMENSION power supply family existing alongside the high featured Q-Line. The CS10.241 includes all the essential basic functions and the devices have a power reserve of 20%. This extra current may even be used continuously at temperatures up to +45°C. The most important features are the small size high efficiency and the wide temperature range. The Auto-select input makes worldwide installation and usage very simple. Defects or system failures caused by wrongly set switches cannot occur. High immunity to transients and power surges as well as low electromagnetic emission and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Electrical durability
(at 40°C; 5A output; 1AC 120Vac input) 99000 hours
(at 40°C; 5A output; 1AC 230Vac input) 118000 hours
(at 25°C; 5A output; 1AC 120Vac input) 281000 hours
(at 25°C; 5A output; 1AC 230Vac input) 334000 hours
(at 40°C; 10A output; 1AC 120Vac input) 50000 hours
(at 40°C; 10A output; 1AC 230Vac input) 82000 hours
(at 25°C; 10A output; 1AC 120Vac input) 141000 hours
(at 25°C; 10A output; 1AC 230Vac input) 233000 hours
(at 40°C; 12A output; 1AC 120Vac input) 34000 hours
(at 40°C; 12A output; 1AC 230Vac input) 53000 hours
(at 25°C; 12A output; 1AC 120Vac input) 97000 hours
(at 25°C; 12A output; 1AC 230Vac input) 149000 hours
(at 40°C; 5A output; 1AC 230Vac input) 118000 hours
(at 25°C; 5A output; 1AC 120Vac input) 281000 hours
(at 25°C; 5A output; 1AC 230Vac input) 334000 hours
(at 40°C; 10A output; 1AC 120Vac input) 50000 hours
(at 40°C; 10A output; 1AC 230Vac input) 82000 hours
(at 25°C; 10A output; 1AC 120Vac input) 141000 hours
(at 25°C; 10A output; 1AC 230Vac input) 233000 hours
(at 40°C; 12A output; 1AC 120Vac input) 34000 hours
(at 40°C; 12A output; 1AC 230Vac input) 53000 hours
(at 25°C; 12A output; 1AC 120Vac input) 97000 hours
(at 25°C; 12A output; 1AC 230Vac input) 149000 hours
Ripple
50mVpp (20Hz...20MHz; 50Ω)
MTBF (Mean Time Between Failures)
638000h (at 40°C; 120Vac input; MTBF SN 29500 IEC 61709)
821000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
542000h (at 40°C; 120Vac input; MTBF SN 29500 IEC 61709)
698000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
1058000h (at 25°C; 120Vac input; MTBF SN 29500 IEC 61709)
1393000h (at 25°C; 230Vac input; MTBF SN 29500 IEC 61709)
447000h (at 40°C; 120Vac input; MTBF MIL HDBK 217F)
472000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
402000h (at 40°C; 120Vac input; MTBF MIL HDBK 217F)
425000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
628000h (at 25°C; 120Vac input; MTBF MIL HDBK 217F)
653000h (at 25°C; 230Vac input; MTBF MIL HDBK 217F)
821000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
542000h (at 40°C; 120Vac input; MTBF SN 29500 IEC 61709)
698000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
1058000h (at 25°C; 120Vac input; MTBF SN 29500 IEC 61709)
1393000h (at 25°C; 230Vac input; MTBF SN 29500 IEC 61709)
447000h (at 40°C; 120Vac input; MTBF MIL HDBK 217F)
472000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
402000h (at 40°C; 120Vac input; MTBF MIL HDBK 217F)
425000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
628000h (at 25°C; 120Vac input; MTBF MIL HDBK 217F)
653000h (at 25°C; 230Vac input; MTBF MIL HDBK 217F)
Time delay
850ms start-up delay (100-230Vac input)
35ms rise time (nominal input; constant full current load; 0mF load capacitance)
75ms rise time (nominal input; constant full current load; 10mF load capacitance)
35ms rise time (nominal input; constant full current load; 0mF load capacitance)
75ms rise time (nominal input; constant full current load; 10mF load capacitance)
Related Documents
Name | Last Update | Language |
---|---|---|
PULS - Power supply units - Catalog.pdf | 01 Oct 2021 | English (US) |
PULS - CS10-241-S1 - Datasheet.pdf | 01 Oct 2021 | English (US) |