PULS
CP5.121
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION CP-series) - 12Vdc-15Vdc (adjustable) / 10A / 120W output - with screw-clamp connections - Single-phase (1AC) or DC input (85Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) / 110Vdc-150Vdc (120Vdc / 127Vdc)) - DIN rail mounting (32mm width) - equivalent to #CP5121
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
CP5.121
Online Price
$250.00
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
CP5.121
Description
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION CP-series) - 12Vdc-15Vdc (adjustable) / 10A / 120W output - with screw-clamp connections - Single-phase (1AC) or DC input (85Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) / 110Vdc-150Vdc (120Vdc / 127Vdc)) - DIN rail mounting (32mm width) - equivalent to #CP5121
Specifications
Primary brand
PULS
Main function
Power supply unit
Product series / family name
DIMENSION series
Sub-range name
CP-series
Functions
AC/DC Power supply unit (PSU) / converter
20% power reserve
20% power reserve
Design
20% power reserve
DC-OK rly. contact output
DC-OK rly. contact output
Supply voltage (AC)
85Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz)
80Vac turn-ON voltage
74Vac shutdown voltage
80Vac turn-ON voltage
74Vac shutdown voltage
Supply voltage (DC)
110Vdc-150Vdc (120Vdc / 127Vdc)
Display
"DC-OK" LED
Type of network
Single-phase (1AC) or DC
Rated current
10A (at 12Vdc)
Rated power
120W
Output voltage (DC)
12Vdc-15Vdc (adjustable)
200mV turn-ON overshoot
200mV turn-ON overshoot
Hold time
35ms (buffer time at 120/230Vac input)
Connection type
screw-clamp connections
Protection functions
output overvoltage protection (16.2Vdc typ. / 17Vdc max.)
Overload / short-circuit current -- 5A max. (R.M.S.) current / (typ. 15A) intermitted current peak for typ. 1s at load impedance 50mΩ
Series / parallel operation -- devices of the same type can be connected in series for higher output voltages / Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the same value (+/-100mV) with the same load conditions on all devices (or the devices can be left with the factory settings). Devices can be paralleled for 1+1 redundancy to gain higher system availability using a redundancy module
Back-feeding loads max. 25V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
Overload / short-circuit current -- 5A max. (R.M.S.) current / (typ. 15A) intermitted current peak for typ. 1s at load impedance 50mΩ
Series / parallel operation -- devices of the same type can be connected in series for higher output voltages / Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the same value (+/-100mV) with the same load conditions on all devices (or the devices can be left with the factory settings). Devices can be paralleled for 1+1 redundancy to gain higher system availability using a redundancy module
Back-feeding loads max. 25V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
Efficiency
0.94 (230Vac input)
0.932 (120Vac input)
0.926 (100Vac input)
0.932 (120Vac input)
0.926 (100Vac input)
Net Width (mm)
32 mm
Mounting mode
DIN rail mounting
Dimensions
W32mm x H124mm x D102mm
Material
Aluminium housing
Ambient air temperature for operation
-25...+70 °C
Current consumption
7A peak max. inrush (at 230Vac input)
7A peak max. inrush (at 120Vac input)
7A peak max. inrush (at 120Vac input)
Power dissipation/losses
(230Vac input; full output load) 7.7 W
(120Vac input; full output load) 8.8 W
(120Vac input; full output load) 8.8 W
Manufacturer product status
Commercialized
Equivalent to
CP5121
Capacitance
(output stage) 2700 μF
Compliant with standard(s)
CE marking
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
Benefits
AC 100-240V Wide-range input
Width only 32mm
Efficiency up to 94%
Excellent partial load efficiency
20% Output power reserve
Easy fuse breaking - 3 times nominal current for 12ms
Safe HiccupPLUS overload mode
Active power factor correction (PFC)
Minimal inrush current surge
Full power between -25°C and +60°C
DC-OK relay contact
3 Year warranty
The Dimension CP-Series are cost optimized power supplies without compromising quality reliability and performance. The CP-Series is part of the DIMENSION power supply family. The most outstanding features of this unit is the small size the high efficiency the electronic inrush current limitation active PFC and the wide operational temperature range. The device has a power reserve of 20% included which may even be used continuously at temperatures up to +45°C. Additionally it can deliver 3 times the nominal output current for 12ms which helps to trip fuses on faulty output branches. High immunity to transients and power surges as well as low electromagnetic emission a DC-OK signal contact for remote monitoring and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Width only 32mm
Efficiency up to 94%
Excellent partial load efficiency
20% Output power reserve
Easy fuse breaking - 3 times nominal current for 12ms
Safe HiccupPLUS overload mode
Active power factor correction (PFC)
Minimal inrush current surge
Full power between -25°C and +60°C
DC-OK relay contact
3 Year warranty
The Dimension CP-Series are cost optimized power supplies without compromising quality reliability and performance. The CP-Series is part of the DIMENSION power supply family. The most outstanding features of this unit is the small size the high efficiency the electronic inrush current limitation active PFC and the wide operational temperature range. The device has a power reserve of 20% included which may even be used continuously at temperatures up to +45°C. Additionally it can deliver 3 times the nominal output current for 12ms which helps to trip fuses on faulty output branches. High immunity to transients and power surges as well as low electromagnetic emission a DC-OK signal contact for remote monitoring and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Electrical durability
(at 40°C; 5A output; 1AC 120Vac input) 297000 hours
(at 40°C; 5A output; 1AC 230Vac input) 294000 hours
(at 25°C; 5A output; 1AC 120Vac input) 839000 hours
(at 25°C; 5A output; 1AC 230Vac input) 833000 hours
(at 40°C; 10A output; 1AC 120Vac input) 94000 hours
(at 40°C; 10A output; 1AC 230Vac input) 110000 hours
(at 25°C; 10A output; 1AC 120Vac input) 267000 hours
(at 25°C; 10A output; 1AC 230Vac input) 311000 hours
(at 40°C; 12A output; 1AC 120Vac input) 51000 hours
(at 40°C; 12A output; 1AC 230Vac input) 61000 hours
(at 25°C; 12A output; 1AC 120Vac input) 143000 hours
(at 25°C; 12A output; 1AC 230Vac input) 171000 hours
(at 40°C; 5A output; 1AC 230Vac input) 294000 hours
(at 25°C; 5A output; 1AC 120Vac input) 839000 hours
(at 25°C; 5A output; 1AC 230Vac input) 833000 hours
(at 40°C; 10A output; 1AC 120Vac input) 94000 hours
(at 40°C; 10A output; 1AC 230Vac input) 110000 hours
(at 25°C; 10A output; 1AC 120Vac input) 267000 hours
(at 25°C; 10A output; 1AC 230Vac input) 311000 hours
(at 40°C; 12A output; 1AC 120Vac input) 51000 hours
(at 40°C; 12A output; 1AC 230Vac input) 61000 hours
(at 25°C; 12A output; 1AC 120Vac input) 143000 hours
(at 25°C; 12A output; 1AC 230Vac input) 171000 hours
Ripple
50mVpp (20Hz...20MHz; 50Ω)
MTBF (Mean Time Between Failures)
687000h (at +40°C; full output; 1AC 120Vac input; MTBF SN 29500 IEC 61709)
732000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
1221000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
1294000h (at +25°C; full output; 1AC 230Vac input; MTBF SN 29500 IEC 61709)
290000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
308000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
421000h (at +25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
447000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
69000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
73000h (at +40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
93000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
99000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF25)
732000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
1221000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
1294000h (at +25°C; full output; 1AC 230Vac input; MTBF SN 29500 IEC 61709)
290000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
308000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
421000h (at +25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
447000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
69000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
73000h (at +40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
93000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
99000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF25)
Time delay
350-400ms start-up delay (100-230Vac input)
30ms rise time (nominal input; constant full current load; 0mF load capacitance)
50ms rise time (nominal input; constant full current load; 10mF load capacitance)
30ms rise time (nominal input; constant full current load; 0mF load capacitance)
50ms rise time (nominal input; constant full current load; 10mF load capacitance)