PULS
CP20.481
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION CP-series) - 48Vdc-56Vdc (adjustable) / 10A / 480W output - with screw-clamp connections - Single-phase (1AC) or DC input (85Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) / 88Vdc-180Vdc (100Vdc / 110Vdc / 120Vdc / 127Vdc nom.)) - DIN rail mounting (48mm width) - equivalent to #CP20481
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
CP20.481
Online Price
$460.00
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
CP20.481
Description
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION CP-series) - 48Vdc-56Vdc (adjustable) / 10A / 480W output - with screw-clamp connections - Single-phase (1AC) or DC input (85Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) / 88Vdc-180Vdc (100Vdc / 110Vdc / 120Vdc / 127Vdc nom.)) - DIN rail mounting (48mm width) - equivalent to #CP20481
Specifications
Primary brand
PULS
Main function
Power supply unit
Product series / family name
DIMENSION series
Sub-range name
CP-series
Functions
AC/DC Power supply unit (PSU) / converter
20% power reserve
20% power reserve
Design
20% power reserve
DC-OK rly. contact output
DC-OK rly. contact output
Supply voltage (AC)
85Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz)
82Vac turn-ON voltage
72Vac shutdown voltage
82Vac turn-ON voltage
72Vac shutdown voltage
Supply voltage (DC)
88Vdc-180Vdc (100Vdc / 110Vdc / 120Vdc / 127Vdc nom.)
Display
"DC-OK" LED
Type of network
Single-phase (1AC) or DC
Rated current
10A (at 48Vdc)
Rated power
480W
Output voltage (DC)
48Vdc-56Vdc (adjustable)
500mV turn-ON overshoot
500mV turn-ON overshoot
Hold time
32ms (buffer time at 120/230Vac input)
Connection type
screw-clamp connections
Protection functions
output overvoltage protection (58.5Vdc typ. / 60Vdc max.)
Overload / short-circuit current -- 4.7A max. (R.M.S.) current / (typ. 15A) intermitted current peak for typ. 2s at load impedance 10mΩ
Series / parallel operation -- devices of the same type can be connected in series for higher output voltages / Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the same value (+/-100mV) with the same load conditions on all devices (or the devices can be left with the factory settings). Devices can be paralleled for 1+1 redundancy to gain higher system availability using a redundancy module
Back-feeding loads max. 63V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
Overload / short-circuit current -- 4.7A max. (R.M.S.) current / (typ. 15A) intermitted current peak for typ. 2s at load impedance 10mΩ
Series / parallel operation -- devices of the same type can be connected in series for higher output voltages / Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the same value (+/-100mV) with the same load conditions on all devices (or the devices can be left with the factory settings). Devices can be paralleled for 1+1 redundancy to gain higher system availability using a redundancy module
Back-feeding loads max. 63V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
Efficiency
0.963 (230Vac input)
0.95 (120Vac input)
0.944 (100Vac input)
0.95 (120Vac input)
0.944 (100Vac input)
Net Width (mm)
48 mm
Mounting mode
DIN rail mounting
Dimensions
W48mm x H124mm x D127mm
Material
Aluminium housing
Ambient air temperature for operation
-25...+70 °C
Current consumption
5.5A peak max. inrush (at 230Vac input)
12A peak max. inrush (at 120Vac input)
12A peak max. inrush (at 120Vac input)
Power dissipation/losses
(230Vac input; full output load) 18.4 W
(120Vac input; full output load) 25.1 W
(120Vac input; full output load) 25.1 W
Power factor (cos phi)
(230Vac input) 0.98
(120Vac input) 0.996
(120Vac input) 0.996
Manufacturer product status
Commercialized
Equivalent to
CP20481
Capacitance
(output stage) 2500 μF
Compliant with standard(s)
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
Benefits
AC 100-240V Wide-range input
Width only 48mm
Efficiency up to 96.3%
Excellent partial load efficiency
20% Output power reserve
Safe HiccupPLUS overload mode
Easy fuse breaking - 3 times nominal current for 12ms
Active power factor correction (PFC)
Minimal inrush current surge
Full power between -25°C and +60°C
DC-OK relay contact
Current sharing feature for parallel use
3 Year warranty
The Dimension CP-Series are cost optimized power supplies without compromising quality reliability and performance. The CP-Series is part of the DIMENSION power supply family. The most outstanding features of CP20.481 are the high efficiency electronic inrush current limitation active PFC wide operational temperature range. The small size is achieved by a synchronous rectification LLC technology and by many further technological design details. The C-Series includes all the essential basic functions The device has a power reserve of 20% included which may even be used continuously at temperatures up to +45°C. Additionally the CP20.481 can deliver about 3 times the nominal output current for 12ms which helps to trip fuses on faulty output branches. High immunity to transients and power surges as well as low electromagnetic emission a DC-OK relay contact and a large international approval package make this unit suitable for nearly every situation.
Width only 48mm
Efficiency up to 96.3%
Excellent partial load efficiency
20% Output power reserve
Safe HiccupPLUS overload mode
Easy fuse breaking - 3 times nominal current for 12ms
Active power factor correction (PFC)
Minimal inrush current surge
Full power between -25°C and +60°C
DC-OK relay contact
Current sharing feature for parallel use
3 Year warranty
The Dimension CP-Series are cost optimized power supplies without compromising quality reliability and performance. The CP-Series is part of the DIMENSION power supply family. The most outstanding features of CP20.481 are the high efficiency electronic inrush current limitation active PFC wide operational temperature range. The small size is achieved by a synchronous rectification LLC technology and by many further technological design details. The C-Series includes all the essential basic functions The device has a power reserve of 20% included which may even be used continuously at temperatures up to +45°C. Additionally the CP20.481 can deliver about 3 times the nominal output current for 12ms which helps to trip fuses on faulty output branches. High immunity to transients and power surges as well as low electromagnetic emission a DC-OK relay contact and a large international approval package make this unit suitable for nearly every situation.
Electrical durability
(at 40°C; 5A output; 1AC 120Vac input) 152000 hours
(at 40°C; 5A output; 1AC 230Vac input) 180000 hours
(at 25°C; 5A output; 1AC 120Vac input) 431000 hours
(at 25°C; 5A output; 1AC 230Vac input) 509000 hours
(at 40°C; 10A output; 1AC 120Vac input) 66000 hours
(at 40°C; 10A output; 1AC 230Vac input) 110000 hours
(at 25°C; 10A output; 1AC 120Vac input) 188000 hours
(at 25°C; 10A output; 1AC 230Vac input) 311000 hours
(at 40°C; 12A output; 1AC 120Vac input) 45000 hours
(at 40°C; 12A output; 1AC 230Vac input) 89000 hours
(at 25°C; 12A output; 1AC 120Vac input) 128000 hours
(at 25°C; 12A output; 1AC 230Vac input) 251000 hours
(at 40°C; 5A output; 1AC 230Vac input) 180000 hours
(at 25°C; 5A output; 1AC 120Vac input) 431000 hours
(at 25°C; 5A output; 1AC 230Vac input) 509000 hours
(at 40°C; 10A output; 1AC 120Vac input) 66000 hours
(at 40°C; 10A output; 1AC 230Vac input) 110000 hours
(at 25°C; 10A output; 1AC 120Vac input) 188000 hours
(at 25°C; 10A output; 1AC 230Vac input) 311000 hours
(at 40°C; 12A output; 1AC 120Vac input) 45000 hours
(at 40°C; 12A output; 1AC 230Vac input) 89000 hours
(at 25°C; 12A output; 1AC 120Vac input) 128000 hours
(at 25°C; 12A output; 1AC 230Vac input) 251000 hours
Ripple
50mVpp (20Hz...20MHz; 50Ω)
MTBF (Mean Time Between Failures)
443000h (at +40°C; full output; 1AC 120Vac input; MTBF SN 29500 IEC 61709)
540000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
810000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
973000h (at +25°C; full output; 1AC 230Vac input; MTBF SN 29500 IEC 61709)
209000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
244000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
283000h (at +25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
334000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
45000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
54000h (at +40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
59000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
72000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF25)
540000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
810000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
973000h (at +25°C; full output; 1AC 230Vac input; MTBF SN 29500 IEC 61709)
209000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
244000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
283000h (at +25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
334000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
45000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
54000h (at +40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
59000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
72000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF25)
Time delay
450ms start-up delay (100-230Vac input)
120ms rise time (nominal input; constant full current load; 0mF load capacitance)
170ms rise time (nominal input; constant full current load; 10mF load capacitance)
120ms rise time (nominal input; constant full current load; 0mF load capacitance)
170ms rise time (nominal input; constant full current load; 10mF load capacitance)
Related Documents
Name | Last Update | Language |
---|---|---|
PULS - Power supply units - Catalog.pdf | 01 Oct 2021 | English (US) |
PULS - CP20-481-2 - Datasheet.pdf | 01 Oct 2021 | English (US) |