PULS
CP10.361
AC/DC Power supply unit (PSU) / converter with ATEX approval - 20% power reserve - PULS (DIMENSION CP-series) - 36Vdc-42Vdc (adjustable) / 6.7A / 240W output - with screw-clamp connections - Single-phase (1AC) or DC input (85Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) / 88Vdc-180Vdc (100Vdc / 110Vdc / 120Vdc / 127Vdc nom.)) - DIN rail mounting (39mm width) - equivalent to #CP10361
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
CP10.361
Online Price
$330.00
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
CP10.361
Description
AC/DC Power supply unit (PSU) / converter with ATEX approval - 20% power reserve - PULS (DIMENSION CP-series) - 36Vdc-42Vdc (adjustable) / 6.7A / 240W output - with screw-clamp connections - Single-phase (1AC) or DC input (85Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz) / 88Vdc-180Vdc (100Vdc / 110Vdc / 120Vdc / 127Vdc nom.)) - DIN rail mounting (39mm width) - equivalent to #CP10361
Specifications
Primary brand
PULS
Main function
Power supply unit
Product series / family name
DIMENSION series
Sub-range name
CP-series
Functions
AC/DC Power supply unit (PSU) / converter
20% power reserve
20% power reserve
Design
ATEX approval
20% power reserve
DC-OK rly. contact output
20% power reserve
DC-OK rly. contact output
Supply voltage (AC)
85Vac-264Vac (100Vac / 110Vac / 120Vac / 200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz)
80Vac turn-ON voltage
70Vac shutdown voltage (steady-state; no load)
55Vac shutdown voltage (dynamic value)
80Vac turn-ON voltage
70Vac shutdown voltage (steady-state; no load)
55Vac shutdown voltage (dynamic value)
Supply voltage (DC)
88Vdc-180Vdc (100Vdc / 110Vdc / 120Vdc / 127Vdc nom.)
Display
"DC-OK" LED
Type of network
Single-phase (1AC) or DC
Rated current
6.7A (at 36Vdc)
Rated power
240W
Output voltage (DC)
36Vdc-42Vdc (adjustable)
200mV turn-ON overshoot
200mV turn-ON overshoot
Hold time
38ms (buffer time at 120/230Vac input)
Connection type
screw-clamp connections
Protection functions
output overvoltage protection (46Vdc typ. / 48Vdc max.)
Overload / short-circuit current -- 3.1A average (R.M.S.) current / min. 19.5A (typ. 21.5A) up to 12ms at load impedance <75mΩ
Series / parallel operation -- devices of the same type can be connected in series for higher output voltages / Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the same value (+/-100mV) with the same load conditions on all devices (or the devices can be left with the factory settings). Devices can be paralleled for 1+1 redundancy to gain higher system availability using a redundancy module
Back-feeding loads max. 50V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
Overload / short-circuit current -- 3.1A average (R.M.S.) current / min. 19.5A (typ. 21.5A) up to 12ms at load impedance <75mΩ
Series / parallel operation -- devices of the same type can be connected in series for higher output voltages / Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the same value (+/-100mV) with the same load conditions on all devices (or the devices can be left with the factory settings). Devices can be paralleled for 1+1 redundancy to gain higher system availability using a redundancy module
Back-feeding loads max. 50V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
Efficiency
0.954 (230Vac input)
0.938 (120Vac input)
0.931 (100Vac input)
0.938 (120Vac input)
0.931 (100Vac input)
Net Width (mm)
39 mm
Mounting mode
DIN rail mounting
Dimensions
W39mm x H124mm x D117mm
Material
Aluminium housing
Ambient air temperature for operation
-25...+70 °C
Current consumption
11A peak max. inrush (at 230Vac input)
7A peak max. inrush (at 120Vac input)
7A peak max. inrush (at 120Vac input)
Power dissipation/losses
(230Vac input; full output load) 11.6 W
(120Vac input; full output load) 15.9 W
(120Vac input; full output load) 15.9 W
Power factor (cos phi)
(230Vac input) 0.97
(120Vac input) 0.99
(120Vac input) 0.99
Manufacturer product status
Commercialized
Equivalent to
CP10361
Capacitance
(output stage) 1500 μF
Compliant with standard(s)
CE marking
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
IECEx
ATEX
Class I Div. 2 HazLoc
GL Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
IECEx
ATEX
Class I Div. 2 HazLoc
GL Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
Benefits
AC 100-240V Wide-range input
Width only 39mm
Efficiency up to 95.4%
Excellent partial load efficiency
20% Output power reserve
Safe HiccupPLUS overload mode
Active power factor correction (PFC)
Minimal inrush current surge
Full power between -25°C and +60°C
DC-OK relay contact
3 Year warranty
The DIMENSION CP-Series units are high-end power supplies in a medium price range without compromising quality reliability and performance. The CP-Series is part of the DIMENSION power supply family. The most outstanding features of CP10.361 are the high efficiency advanced inrush current limitation active PFC and the wide operational temperature range. The CP-Series includes all the essential basic functions. The devices have a power reserve of 20% included which may even be used continuously at temperatures up to +45°C. Additionally the CP10 can deliver 3 times the nominal output current for at least 12ms which helps to trip fuses on faulty output branches. High immunity to transients and power surges as well as low electromagnetic emission; a DC-OK relay contact and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Width only 39mm
Efficiency up to 95.4%
Excellent partial load efficiency
20% Output power reserve
Safe HiccupPLUS overload mode
Active power factor correction (PFC)
Minimal inrush current surge
Full power between -25°C and +60°C
DC-OK relay contact
3 Year warranty
The DIMENSION CP-Series units are high-end power supplies in a medium price range without compromising quality reliability and performance. The CP-Series is part of the DIMENSION power supply family. The most outstanding features of CP10.361 are the high efficiency advanced inrush current limitation active PFC and the wide operational temperature range. The CP-Series includes all the essential basic functions. The devices have a power reserve of 20% included which may even be used continuously at temperatures up to +45°C. Additionally the CP10 can deliver 3 times the nominal output current for at least 12ms which helps to trip fuses on faulty output branches. High immunity to transients and power surges as well as low electromagnetic emission; a DC-OK relay contact and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Electrical durability
(at 40°C; 3.35A output; 1AC 120Vac input) 163000 hours
(at 40°C; 3.35A output; 1AC 230Vac input) 196000 hours
(at 25°C; 6.7A output; 1AC 120Vac input) 87000 hours
(at 25°C; 6.7A output; 1AC 230Vac input) 130000 hours
(at 40°C; 8A output; 1AC 120Vac input) 68000 hours
(at 40°C; 8A output; 1AC 230Vac input) 112000 hours
(at 25°C; 3.35A output; 1AC 120Vac input) 462000 hours
(at 25°C; 3.35A output; 1AC 230Vac input) 553000 hours
(at 40°C; 6.7A output; 1AC 120Vac input) 246000 hours
(at 40°C; 6.7A output; 1AC 230Vac input) 368000 hours
(at 25°C; 8A output; 1AC 120Vac input) 192000 hours
(at 25°C; 8A output; 1AC 230Vac input) 316000 hours
(at 40°C; 3.35A output; 1AC 230Vac input) 196000 hours
(at 25°C; 6.7A output; 1AC 120Vac input) 87000 hours
(at 25°C; 6.7A output; 1AC 230Vac input) 130000 hours
(at 40°C; 8A output; 1AC 120Vac input) 68000 hours
(at 40°C; 8A output; 1AC 230Vac input) 112000 hours
(at 25°C; 3.35A output; 1AC 120Vac input) 462000 hours
(at 25°C; 3.35A output; 1AC 230Vac input) 553000 hours
(at 40°C; 6.7A output; 1AC 120Vac input) 246000 hours
(at 40°C; 6.7A output; 1AC 230Vac input) 368000 hours
(at 25°C; 8A output; 1AC 120Vac input) 192000 hours
(at 25°C; 8A output; 1AC 230Vac input) 316000 hours
Ripple
50mVpp (20Hz...20MHz; 50Ω)
MTBF (Mean Time Between Failures)
560000h (at +40°C; full output; 1AC 120Vac input; MTBF SN 29500 IEC 61709)
661000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
1017000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
1176000h (at +25°C; full output; 1AC 230Vac input; MTBF SN 29500 IEC 61709)
188000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
213000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
252000h (at +25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
290000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
40000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
47000h (at +40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
51000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
61000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF25)
661000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
1017000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
1176000h (at +25°C; full output; 1AC 230Vac input; MTBF SN 29500 IEC 61709)
188000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
213000h (at 40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
252000h (at +25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
290000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
40000h (at 40°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Fixed GF40)
47000h (at +40°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Benign GB40)
51000h (at 25°C; full output; 1AC 120Vac input; MTBF MIL HDBK 217F Ground Benign GB25)
61000h (at 25°C; full output; 1AC 230Vac input; MTBF MIL HDBK 217F Ground Fixed GF25)
Time delay
240-300ms start-up delay (100-230Vac input)
60ms rise time (nominal input; constant full current load; 0mF load capacitance)
120ms rise time (nominal input; constant full current load; 7mF load capacitance)
60ms rise time (nominal input; constant full current load; 0mF load capacitance)
120ms rise time (nominal input; constant full current load; 7mF load capacitance)
Related Documents
Name | Last Update | Language |
---|---|---|
PULS - Power supply units - Catalog.pdf | 01 Oct 2021 | English (US) |
PULS - CP10-361 - Datasheet.pdf | 01 Oct 2021 | English (US) |